ASV SR-70 Servisní příručka Strana 130

  • Stažení
  • Přidat do mých příruček
  • Tisk
  • Strana
    / 141
  • Tabulka s obsahem
  • ŘEŠENÍ PROBLÉMŮ
  • KNIHY
  • Hodnocené. / 5. Na základě hodnocení zákazníků
Zobrazit stránku 129
6. If your reading is low, remove the cap and loosen
the jam nut on the posi-power adjustment screw
and turn it counter clockwise until it stops then
retighten the jam nut. (figure 17-11)
a) If the screw was already turned completely
out and pressure reads lower than specified,
the posi-power relief valve is faulty and should
be replaced.
b) If you were able to turn the screw out, recheck
posi-power pressure to see if the reading is
now within specification. If it is, the system
should function properly. If it did not improve,
the posi-power relief valve is faulty and should
be replaced.
To Adjust Posi-Power:
1. Loosen the jam nut and then turn the screw to
adjust for more or less posi-power function.
(figure 17 -11)
a) Turn the screw clockwise to increase function
and limit pump flow during high load condi-
tions. (less likely to stall)
b) Turn counter-clockwise to decrease function
and maximize pump flow during high load con-
ditions. (more likely to stall)
2. Tighten the jam nut while holding the set screw in
place to keep desired setting.
Auxiliary Flow Test
The PT-70/80 is equipped with both high and low flow
auxiliary circuits. If an auxiliary flow problem is sus-
pected, the following procedures should be performed.
Note: If an auxiliary circuit problem is suspected, per-
form all pressure test and adjustment procedures as
necessary prior to attempting to perform the flow test
procedure. Most issues will be solved with the pres-
sure test and adjustment procedures, but if a problem
still persists after all pressures are correctly set, pro-
ceed with the flow test.
17-6
Rubber Track Loader
17. Hydraulic Pressure & Flow
20
19
18
17
20
25
e +/- 1)
CE/ROW PT-80 Low Flow Auxiliary
0
0
5
10
15
0 psi 1000 psi 2000 psi 2500 psi 3000 psi
GPM (readings ar
System Load
ROW PT
-
80 High Flow Auxiliary
31 31
30
26
25
30
35
e +/-2)
ROW
PT
-
80
High
Flow
Auxiliary
0
5
10
15
20
GPM (readings a
0
0
0 psi 1000 psi 2000 psi 2500 psi 3000 psi
System Load
Required Tools
Flow Meter (with variable loading valve)
0 kPa 6895 kPa 13790 kPa 17240 kPa 20680 kPa
System
load
(76 lpm)
(72 lpm)
(68 lpm)
(64 lpm)
0 kPa 6895 kPa 13790 kPa 17240 kPa 20680 kPa
System
load
(117 lpm) (117 lpm)
(114 lpm)
(98 lpm)
(7.6 lpm)
(7.6 lpm)
PT-70/80 Low Flow Auxiliary
PT-70/80 High Flow Auxiliary
Zobrazit stránku 129
1 2 ... 125 126 127 128 129 130 131 132 133 134 135 ... 140 141

Komentáře k této Příručce

Žádné komentáře